Home / Chiller / Air Cooled Chiller / Air Cooled Chiller CHI21-012

Air Cooled Chiller CHI21-012

Air cooled chiller absorb heat from process water, and the heat is then transferred to the air around the chiller unit. Air cooled chiller require less maintenance.

Used in Laboratory, Pharmaceutical, Chemical, Laser

Also known as Laboratory Air Cooled Chiller

  • It adopts single-stage vapor compression circuit and has compressor overload protection, pump overload protection, reverse phase and lack of phase warning, anti-icing protection, high and low pressure protection and other devices.
  • The machine has stable performance and long life.
  • It can cool down quickly, and the temperature is stable to meet customer requirements.
  • This series of products mainly work on the principle of cold and heat exchange.

Features

  • It adopts single-stage vapor compression circuit and has compressor overload protection, pump overload protection, reverse phase and lack of phase warning, anti-icing protection, high and low pressure protection and other devices.
  • The machine has stable performance and long life.
  • It can cool down quickly, and the temperature is stable to meet customer requirements.
  • This series of products mainly work on the principle of cold and heat exchange.
  • It is suitable for the cooling field in modern industry and is not affected by the ambient temperature.
  • It is an indispensable configuration device.

Specifications

Freezing capacity: 
      kw12.5 kw
      kcal/h10750 kcal/h
      btu/h42650 btu/h
Compressor: 
      Output power3.7 kw
      hp5 hp
      Weight4.3 kg
Refrigerant: 
      Control modeThermostatic expansion valve
      TypeR22 ( R407C optional )
Evaporator(Type)Tube-in-shell
Condenser(Air Chiller): 
      Fan power0.25x2
      TypeHigh effective inner threaded copper finned + low noise fan
Water tank capacity60 L
Pump: 
      TypeStainless steel centrifugal pump
      Power kw0.37 kw
      Flow rate88 l/min
      Working pressure2 bar
      Chilled wateroutlet1 inchx1
Pipe coupling: 
      Chilled water inlet1 inchx1
      Water tank drainage port1/2 inch
Dimension(LXWXH) mm1250X700X1200 mm
Weight175 kg
Power3 ph-380 V/50 Hz (220 V/400 V/415 V/440 V 50 Hz/60 Hz)
Temperature5-35 °C
Tolerance± 0.5 °C (± 1 °C at low load)
Safety protectionsHigh and low pressure controller/anti-freezing switch/overload of pump and compressor protection/overheat protection/delayed protection

Product Inquiry